CDS-1型臭氧水处理塔杀菌效果观察 |
| |
引用本文: | 王洪林,顾建.CDS-1型臭氧水处理塔杀菌效果观察[J].中国消毒学杂志,1995,12(3):155-158. |
| |
作者姓名: | 王洪林 顾建 |
| |
摘 要: | 试验表明,在CDS-1型臭氧水处理塔中,对水中人工污染的大肠杆菌,用0.11mg/L臭氧作用45分钟可杀灭99.99%,对枯草杆菌黑色变种芽胞,用3.11mg/L臭氧作用45分钟可杀灭99.90%。对河水与医院污水中自然菌杀灭效果较差。臭氧产量与水温可影响处理塔的消毒效果。
|
关 键 词: | 水消毒,臭氧,芽胞的杀灭 |
OBSERVATION ON GERMICIDAL EFFICACY OF CDS-1 TYPE EQUIPMENT FOR WATER
DISINFECTION WITH OZONE |
| |
Abstract: | The efficacy of CDS-1 Type Equipment for Water Disinfection with Ozone was
tested.It was indicated that 0.11mg/L ozone with a 45 minute contact time could kill 99.99% of
Fscherichia coli in artificially contaminatedwater and3.11mg/L ozone with a 45 minutecontact
time could kill 99. 90% of spores of Bacillus sublilis、var,niger in the water. Fordisinfection of
contaminated river water,0.11 mg / L ozone with a 45 minute contact timecould reduce the total
bacterial count by 97.17%,while 1.37 mg / L ozone could only reducethe total bacterial count of
hospital sewage by 68.00%. Observation on influencing factors indicated that the influence of
contact time tested onthe germicidal efficacy was insigniflcant.The higher the ozone
concentration,the better thegermicidal efflcacy.Under the conditions of the test,the ozone
concentration in water in-creased with increasing ozone production by the equipment(150~200
g/h)and decreasingwater temperature(20~26℃). |
| |
Keywords: | water disinfection ozone killing of sporeJiangsu Provincial Sanitary and Anti-epidemic Station |
本文献已被 维普 等数据库收录! |
|