Fault Current Limitation in Electrical Power Networks Containing HTS Cable and HTS Fuse
Authors:Pavel N. Degtyarenko  Vladimir V. Zheltov  Nikolay N. Balashov  Andrey Yu. Arkhangelsky  Alena Yu. Degtyarenko  Konstantin L. Kovalev
Affiliation:1.Joint Institute for High Temperature of the Russian Academy of Sciences, Moscow 125412, Russia;2.S-Innovations LLC, Moscow 117246, Russia;3.P.N. Lebedev Physical Institute of the Russian Academy of Sciences, Moscow 119991, Russia;4.Moscow Aviation Institute, National Research University, Moscow 125993, Russia
Abstract:Numerical calculations of parameters of an electrical power network where an HTS fuse is used as a fault current limiting device have been done. The calculations were performed for networks containing different types of HTS cables as well. The design of HTS fuse was developed based on the numerical calculation for the network-rated parameters considering the special types 2G HTS tape characteristics. The distinctive feature of these tapes is the minimal thickness (about 30 µm) of the substrate at the critical current 450–600 A. The tests were performed at a voltage of 1 kV and demonstrated the ability of circuit breaking at fault currents about 3–4 kA. A comparison of experimental results with the calculations allows us to conclude that the HTS fuse of this design can operate as a fault current limiting device in electrical power networks at various rated voltage levels.
Keywords:2G HTS wires   HTS cables   short circuit   HTS Fuse
设为首页 | 免责声明 | 关于勤云 | 加入收藏