A large outbreak of Legionnaires' disease due to an inadequate circulating and filtration system for bath water--epidemiologic manifestations
Authors:Nakamura Hiroyuki  Yagyu Hisanaga  Kishi Koji  Tsuchida Fumihiro  Oh-Ishi Shuji  Yamaguchi Keizo  Matsuoka Takeshi
Institution:Fifth Department of Internal Medicine, Tokyo Medical University, Inashiki, Ibaraki.
Abstract:OBJECTIVE: To study the epidemiologic manifestations of a large outbreak of Legionnaires' disease due to an inadequate circulating and filtration system for bath water. PATIENTS: In June 2000 at Ishioka City, Ibaraki Prefecture, a large outbreak of Legionnaire's disease occurred, as a result of an inadequate circulating and filtration system for communal bath water. This outbreak was the worst ever experienced in Japan, involving a total of 34 patients (20 confirmed, 14 probable), 3 of whom died. MEASUREMENTS AND RESULTS: Legionella pneumophila serogroup 1 was isolated from sputum culture in two patients. Bacteriological culture of the public bath water subsequently yielded large numbers of Legionella species. Cleavage of genomic DNA showed that restriction fragment patterns coming from clinical and environmental isolates of L. pneumophila serogroup 1 were closely related, focusing the inquiry to a public bathhouse where a circulating filtration system was suspected as the source of infection. CONCLUSIONS: It was later concluded that the circulating filtration system adopted for bath water was marred by a serious design flaw that subsequently caused the mass outbreak. Specifically, a line of the bath water was being returned to the bath without undergoing heat exchange or sterilization by chlorine; and the Legionella species that had proliferated in the filter and the bright stone filtration unit were allowed to return to the bath, eventually culminating in a mass infection.
Keywords:
本文献已被 PubMed 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号