层流洁净通风对净化间空气除菌效果的检测
引用本文:郭龙,赵虹彩,郑金光,彭义刚,郭伟.层流洁净通风对净化间空气除菌效果的检测[J].中国消毒学杂志,1999,0(1):35-37.
作者姓名:郭龙  赵虹彩  郑金光  彭义刚  郭伟
作者单位:新疆维吾尔自治区阿克苏农一师医院,阿克苏,843000
摘    要:对医院制剂净化间空气,用经高效空气滤器净化空气进行层流通风30min时.可使细菌总数由496cfu/m3减至189cfu/m3,真菌由385cfu/m3减至126cfu/m3,90min时可使两者分别减至55cfu/m3与33cfu/m3。

关 键 词:空气消毒  层流通风

EXAMINATION OF EFFICACY OF LAMINAR-FLOW CLEAN VENTILATION IN REMOVING BACTERIA IN AIR OF CLEAN ROOM
Guo Long,et al..EXAMINATION OF EFFICACY OF LAMINAR-FLOW CLEAN VENTILATION IN REMOVING BACTERIA IN AIR OF CLEAN ROOM[J].Chinese Journal of Disinfection,1999,0(1):35-37.
Authors:Guo Long  
Institution:Guo Long, et al.
Abstract:When laminar-flow ventilation (the air had been purified by highly efficient air filter) was used for the clean pharmaceutical preparation room in hospital, the total bacterial count could be reduced from 496 cfu/m3 to 189 cfu / m3 and the fungi were reduced from 385 cfu / m3 to 126 cfu / m3 after ventilation for 30 min. They were reduced to 55 cfu /m3 and 33 cfu/m3 respectively after ventilation for 90 min.
Keywords:air disinfection laminar-flow ventilation  