清远市公共场所卒调冷却塔水军团菌污染状况
引用本文:黄惠兴,李桂霞,王平原,徐国洪.清远市公共场所卒调冷却塔水军团菌污染状况[J].职业与健康,2009,25(22):2421-2422.
作者姓名:黄惠兴  李桂霞  王平原  徐国洪
作者单位:广东省清远市疾病预防控制中心,511515
摘    要:目的了解清远市区公共场所集中窄调冷却塔水军团菌污染状况。方法根据《公共场所集中空调通风系统卫生规范》,随机抽取清远市区公共场所24家共135份水样进行军团菌检测。结果17家公共场所59份样品中检出嗜肺军团菌,嗜肺军团菌污染率高达70.8%(17/24),检出率为43.7%(59/135)。结论军团菌存在于公共场所中央空调系统,已对暴露人群的健康造成潜在威胁,应采取有效防范措施。

关 键 词:军团菌  空调冷却水  污染率

Legionella Contamination in Cooling Tower Water of Central Air-conditioning in Public Places in Qingyuan City
Institution:HUANG Hui-xing, LI Gui-xia, WANG Ping-yuan, et al. ( Qingyuan Center for Disease Control and Prevention, Qingyuan 511500, China )
Abstract: Objective] To study the legionella contamination situation in cooling tower water of central air-conditioning in public places in the city of Qingyuan. Methods] According to "Hygienical Standards of Centralized air-conditioning ventilation System in Public Places", 135 samples from 24 public places were randomly selected for the test of legionella. Results] Legionetla pneumophi- la were isolated from 59 samples of 17 public places, the contamination rate was 70.8% ( 17/24) , and the detection rate was 43.7% (59/135}. Conclusion] Legionella exists in 43.7% central air-conditioning system in public places, it becomes a potential threat to the health of exposed population, so some effective measures should be adopted.
Keywords:Legionella  Air-conditioning cooling water  Contamination rate