清远市公共场所集中空调通风系统污染状况
引用本文:李桂霞,海岗,沈政,冯贤惠,王平原,明剑辉,林凤娣,陈丽萍,黎晓红,黎智怡.清远市公共场所集中空调通风系统污染状况[J].职业与健康,2008,24(18):1924-1925.
作者姓名:李桂霞  海岗  沈政  冯贤惠  王平原  明剑辉  林凤娣  陈丽萍  黎晓红  黎智怡
作者单位:广东省清远市疾病预防控制中心,511500
摘    要:目的了解清远市区集中空调通风系统送风微生物污染状况。方法于2007年采集济远市区14家宾馆、酒店的集中式空调系统125个送风口,分别进行细菌总数、真菌总数、B-溶血性链球菌检测。结果所调查的14家单位有9家微生物超标,合格率为35.7%;125个空调送风口有21个点微生物超标,合格率为83.2%。结论清远市区宾馆、酒店集中空调系统送风微生物污染较为严重,应加强公共场所集中空调系统的卫生监督管理。

关 键 词:微生物污染  空调系统  送风口

Investigation of the Microorganism Contamination of the Centralized Air Conditioning System in the Public Places of Qingyuan City
LI Gui-xia,HAI Gang,SHEN Zheng,FENG Xian-hui,WANG Ping-yuan,MING Jian-hui,LIN Feng-di,CHEN Li-ping,LI Xiao-hong,LI Zhi-yi.Investigation of the Microorganism Contamination of the Centralized Air Conditioning System in the Public Places of Qingyuan City[J].Occupation and Health,2008,24(18):1924-1925.
Authors:LI Gui-xia  HAI Gang  SHEN Zheng  FENG Xian-hui  WANG Ping-yuan  MING Jian-hui  LIN Feng-di  CHEN Li-ping  LI Xiao-hong  LI Zhi-yi
Institution:[ Qingyuan Center for Disease Control and Prevention, Guangdong, 511500, China)
Abstract: Objective] To study the microorganism contamination of the centralized air conditioning system in Qingyuan. Methods] Samples were collected from 125 draught holes in the centralized air conditioning system of 14 hotels in Qingyuan City in 2007 ; detection was conducted on the bacterial counting, epiphyte counting and 13 Streptococcus hemolyticus. Results] The microorganism in 9 investigated hotels exceeded the standard with an eligible rate of 35.7%, that in 21 draught holes exceeded the standard with an eligible rate of 83.2%. Conclusion] The microorganism contamination of the centralized air conditioning system is quite serious; sanitary supervision should be enhanced in the public places of Qingyuan.
Keywords:Microorganism contamination  Air conditioning system  Draught holes