2007—2011年上海市某区公共场所集中空调通风系统监测结果分析
引用本文:张之幸,邬颖麒,沈隽,郑频频,高俊岭. 2007—2011年上海市某区公共场所集中空调通风系统监测结果分析[J]. 职业与健康, 2012, 28(7): 872-874
作者姓名:张之幸  邬颖麒  沈隽  郑频频  高俊岭
作者单位:1. 上海市长宁区卫生局卫生监督所环境卫生监督科,200051
2. 复旦大学公共卫生学院
摘    要:
目的了解上海市某区公共场所集中空调卫生状况,为今后开展公共场所集中空调卫生监督监测提供工作依据。方法对2007—2011年某区公共场所集中空调卫生监测资料进行汇总分析。结果风管中积尘量合格率为87.08%,细菌、真菌总数合格率分别为87.64%、95.51%;送风中PM10合格率为75.84%;送风中细菌,真菌总数合格率分别为63.48%、82.02%,β-溶血性链球菌检测均为阴性。结论该区公共场所集中空调通风系统内各环节均存在不同程度污染,对人群健康构成潜在的危害,通过清洗消毒可大幅度降低污染水平。应加强卫生监管,加大卫生监督管理力度。

关 键 词:公共场所  集中空调通风系统  监督监测

Analysis of monitoring results of central ventilation and air conditioning systems in public places of a district of Shanghai City from 2007-2011
ZHANG Zhi-xing , WU Ying-qi , SHEN Juan , ZHENG Pin-pin , GAO Jun-ling. Analysis of monitoring results of central ventilation and air conditioning systems in public places of a district of Shanghai City from 2007-2011[J]. Occupation and Health, 2012, 28(7): 872-874
Authors:ZHANG Zhi-xing    WU Ying-qi    SHEN Juan    ZHENG Pin-pin    GAO Jun-ling
Affiliation:*Supervision Department of Environmental Health,Changning District Institute for Health Inspection,Shanghai,200051,China
Abstract:
[Objective]To understand the sanitation conditions of central ventilation and air conditioning systems in public places of a District of Shanghai,and provide the evidence for its sanitary supervision and surveillance [Methods]Data about central ventilation and air conditioning systems from 2007-2011 was collected and analyzed. [Results]The qualified rate of deposit dust amount in vent pipe,total bacterial count and total fungi count was 87.08%,87.64%,95.51%,respectively.The qualified rate of total bacterial count,total fungi count and PM10 level in blowing air was 63.48%,82.02% and 75.84% respectively.β hemolytic streptococcus ware not detected. [Conclusion]Different degrees of contamination exist in central ventilation and air conditioning systems in public places,which possess the potential danger to public health.Cleaning and disinfection can greatly reduce the contamination level.The hygiene supervision and management should be strengthened in the future.
Keywords:Public places  Central ventilation and air conditioning systems  Inspection and monitoring