四种空气采样方法检测层流病房动态环境结果比较
引用本文:赵心懋,袁晓宁,徐欣欣,申玉玲. 四种空气采样方法检测层流病房动态环境结果比较[J]. 中国消毒学杂志, 2007, 24(2): 115-117
作者姓名:赵心懋  袁晓宁  徐欣欣  申玉玲
作者单位:北京大学第三医院感染管理科,北京,100083
摘    要:
目的调查我院使用中的层流洁净病房的空气质量,比较四种采样方法的相关性。方法用平板沉降法、LWC-Ⅰ型离心式空气微生物采样器、JWL-ⅡB型和JWL-ⅡC型撞击式空气微生物监测仪等4种采样方法进行了检测比较。结果本医院层流洁净病房空气中自然菌总数符合Ⅱ类环境要求。4种空气采样方法采集到的平均细菌总数由平板沉降法~JWL-ⅡC型撞击式采样器依次为:75 cfu/m3、96 cfu/m3、85 cfu/m3和104 cfu/m3,各方法之间无明显差别。JWL-ⅡC型撞击式多功能空气微生物监测仪与平皿沉降法的结果一致率最好(73.0%)。结论4种空气采样方法的采样检测结果无显著差异(P>0.05),该医院外科层流洁净病房的空气含菌量符合Ⅱ类环境要求,达到国家规定10万级层流洁净病房的要求。

关 键 词:层流空气  层流病房  采样方法  空气质量
文章编号:1001-7658(2007)02-0115-03
修稿时间:2006-08-08

COMPARISON OF THE RESULTS OF MONITORING THE ENVIRONMENT OF LAMINAR-FLOW WARD BY FOUR KINDS OF AIR SAMPLING METHODS
ZHAO Xin-mao,YUAN Xiao-ning,XU Xin-xin,SHEN Yu-ling. COMPARISON OF THE RESULTS OF MONITORING THE ENVIRONMENT OF LAMINAR-FLOW WARD BY FOUR KINDS OF AIR SAMPLING METHODS[J]. Chinese Journal of Disinfection, 2007, 24(2): 115-117
Authors:ZHAO Xin-mao  YUAN Xiao-ning  XU Xin-xin  SHEN Yu-ling
Affiliation:Department of Nosocomial Infection Control, Third Clinical Hospital, Beijing University, Beijing 100083, China
Abstract:
Objective To investigate the air quality of the laminar-flow clean ward used in this hospital and to compare the relations to four sampling methods. Methods The monitoring results using four sampling methods including flat slab exposure method,LWC Type-1 Centrifugal Sampler of air microorganisms,JWL Type-ⅡB and JWL Type-ⅡC Clash Sampler of air microorganisms were compared. Results The total natural bacterial count in air of laminar-flow clean ward of this hospital fulfilled the requirement of class-Ⅱenvironment.The average total bacterial counts collected by the 4 air sampling methods in order from flat slab exposure method to JWL Type-ⅡC Clash Sampler of air microorganisms were 75 cfu/m3,96 cfu/m3,85 cfu/m3 and 104 cfu/m3,with no significant difference between the different methods.The conformation rate between the results of JWL Type-ⅡC Clash Multifunctional Sampler of air microorganisms and flat slab exposure method was the best(73.0%). Conclusions The monitoring results of sampling by 4 air sampling methods had no significant difference(P>0.05).The bacteria content in air of surgical laminar-flow clean ward in this hospital fulfilled the requirement of class-Ⅱ environment and the requirement of state-specified 105-grade laminar-flow clean ward.
Keywords:laminar-flow air   laminar -flow ward   sampling method   air quality